Hotels and motels; installation of smoke detectors
Sec. 3. (a) This section only applies to hotels and motels.
(b) All hotels and motels must have functional smoke detectors.
(c) Except as provided in subsection (f), a detector must be
installed in all interior corridors adjacent to sleeping rooms and must
be spaced no farther apart than thirty (30) feet on center, or more
than fifteen (15) feet from any wall.
(d) The detectors must be hard wired into a building's electrical
system, except as provided in subsection (f).
(e) The detectors must be wired in a manner that activates all the
devices in a corridor when one (1) is activated, except as provided in
subsection (f).
(f) All single level dwellings, all seasonably occupied dwellings,
and all hotels and motels with twelve (12) sleeping rooms or less
(and containing no interior corridors) are exempt from the
requirements of subsections (c), (d), and (e). In all such units:
(1) a detector must be installed in each sleeping room; and
(2) the detector may be battery operated.
If a battery operated detector is installed, it must contain a tamper
resistant cover to protect the batteries. The fire marshal shall adopt
rules detailing the specifications for the tamper resistant cover. If a
battery operated detector is not installed, the detector must be hard
wired into a building's electrical system.
As added by Acts 1982, P.L.141, SEC.1. Amended by P.L.237-1983,
SEC.3; P.L.176-1991, SEC.3.
Last modified: May 27, 2006