Sec. 232.109. FIRE SUPPRESSION SYSTEM. In a subdivision that is not served by fire hydrants as part of a centralized water system certified by the Texas Commission on Environmental Quality as meeting minimum standards for water utility service, the commissioners court may require a limited fire suppression system that requires a developer to construct:
(1) for a subdivision of fewer than 50 houses, 2,500 gallons of storage; or
(2) for a subdivision of 50 or more houses, 2,500 gallons of storage with a centralized water system or 5,000 gallons of storage.
Added by Acts 2007, 80th Leg., R.S., Ch. 1390 (S.B. 1867), Sec. 5, eff. September 1, 2007.
Section: Previous 232.091 232.092 232.093 232.094 232.095 232.096 232.097 232.101 232.102 232.103 232.104 232.105 232.106 232.107 232.108Last modified: September 28, 2016