§ 45.1-161.188. Grounding

A. All metallic sheaths, armors, and conduits enclosing power conductors shall be electrically continuous throughout and shall be grounded effectively.

B. Metallic frames, casing, and other enclosures of stationary electric equipment that can become "alive" through failure of insulation or by contact with energized parts shall be grounded effectively, or equivalent protection shall be provided.

C. Three-phase alternating current circuits used underground shall contain either a direct or derived neutral which shall be grounded through a suitable resistor at the power center, and a grounding circuit, originating at the grounded side of the grounding resistor, shall extend with the power conductors and serve as the grounding conductor for the frames of all the electrical equipment supplied power from that circuit. High-voltage circuits extending underground shall be supplied with a grounding resistor of a proper Ohmic value located on the surface to limit the voltage drop in the grounding circuit external to the resistor to not more than 100 volts under fault conditions. The grounding resistor shall be rated for maximum fault current continuously and insulated from ground for a voltage equal to the phase-to-phase voltage of the system. All resistance-grounded alternating circuits used underground shall include a fail-safe ground check circuit to monitor continuously the grounding circuit to assure the continuity of the ground conductor.

(1966, c. 594, § 45.1-79; 1994, c. 28; 1999, c. 256.)

Sections:  Previous  45.1-161.181  45.1-161.182  45.1-161.183  45.1-161.184  45.1-161.185  45.1-161.186  45.1-161.187  45.1-161.188  45.1-161.189  45.1-161.190  45.1-161.191  45.1-161.192  45.1-161.193  45.1-161.194  45.1-161.195  Next

Last modified: April 3, 2009