Ex Parte TSUCHIYA et al - Page 4




               Appeal No. 2001-2186                                                                        Page 4                
               Application No. 08/674,865                                                                                        


                      The specification indicates that the “the angle” referenced in claim 14 is the angle created               
               by placing the terminals around the circumference of the heating portion 21, i.e., the angle                      
               between two lines extending from adjacent terminals to the center point of the circle (Fig. 2,                    
               reference numbers 22, 23, 24, 25).  The specification distinguishes the location of the terminals                 
               from the prior art by noting that Appellants’ terminals are arranged at equal intervals along the                 
               circumferential direction of the heating portion 21 whereas the prior art terminals are arranged at               
               an angle of 180° in the circumferential direction of the heating portion (specification at 19, ll. 1-             
               10 in combination with 15, ll. 11-20 and 4, ll. 19-24; also compare Fig. 2 at 22, 23, 24, 25 with                 
               Fig. 9 at 106, 107).  The equal intervals described and depicted in the specification are equivalent              
               to an angle of 90° as measured from the center point of the circle.  Reading the claim consistently               
               with the specification requires that the terminals be placed substantially in the described and                   
               depicted equidistant arrangement.                                                                                 
                      The Examiner relies on Wilsey as evidence that the terminal arrangement required by the                    
               claims was known in the prior art.  Wilsey does not have electrode connecting terminals arranged                  
               as claimed.  In Wilsey, pairs of terminals are arranged substantially 180° from each other.  As                   
               discussed above, the claims require a 90° spacing in relation to the circumference of the                         
               cylindrical heater.                                                                                               
                      The Examiner has not established that each and every limitation of the claim is described                  
               or suggested by the combination of prior art references or would have been obvious based on the                   
               knowledge of those of ordinary skill in the art and, thus, the Examiner has failed to establish a                 







Page:  Previous  1  2  3  4  5  6  7  Next 

Last modified: November 3, 2007