Illinois Compiled Statutes 430 ILCS 75 Boiler and Pressure Vessel Safety Act. Section 5

    (430 ILCS 75/5) (from Ch. 111 1/2, par. 3206)

    Sec. 5. Exemptions.

    (a) This Act shall not apply to the following boilers and pressure vessels:

        (1) Boilers and pressure vessels under federal

    regulations, except for boiler and pressure vessels in nuclear facilities subject to Section 2a, and boilers and pressure vessels located in cities of more than 500,000 inhabitants.

        (2) Pressure vessels used for transportation and

    storage of compressed or liquefied gases when constructed in compliance with specifications of the Department of Transportation and charged with gas or liquid, marked, maintained, and periodically requalified for use, as required by appropriate regulations of the Department of Transportation.

        (3) Pressure vessels located on vehicles operating

    under the rules of other State authorities and used for carrying passengers or freight.

        (4) Pressure vessels installed on the right of way of

    railroads and used directly in the operation of trains.

        (5) Boilers and pressure vessels under the inspection

    jurisdiction of the Department of Natural Resources and located on mine property.

        (6) Boilers and pressure vessels located on farms and

    used solely for agricultural purposes.

        (7) Steam boilers of a miniature model locomotive,

    boat, tractor, or stationary engine constructed and maintained as a hobby and not for commercial use, that have an inside diameter not exceeding 12 inches and a grate area not exceeding 1 1/2 square feet, provided they are constantly attended while in operation and are equipped with a water level indicator, pressure gauge, and a safety valve of adequate capacity.

        (8) Pressure vessels regulated and inspected under

    the Illinois Fertilizer Act of 1961.

        (9) Pressure vessels containing liquefied petroleum

    gas regulated under the Liquefied Petroleum Gas Regulation Act.

    (b) The following boilers and pressure vessels shall be exempt from the requirements of Sections 10, 11, 12, and 13 of this Act:

        (1) Steam boilers used for heating purposes and

    operated at a pressure not in excess of 15 pounds per square inch gauge (psig) and having a rating not in excess of 200,000 B.T.U. per hour input.

        (2) Hot water heating boilers operated at a pressure

    not in excess of 30 psig and having a rating not in excess of 200,000 B.T.U. per hour.

        (3) Boilers and pressure vessels, located in private

    residences or in multi-family buildings having fewer than 6 dwelling units.

        (4) Hot water supply boilers that are directly fired

    with oil, gas, or electricity when none of the following limitations are exceeded:

            (A) Heat input of 200,000 BTU per hour.

            (B) Water temperature of 200 degrees Fahrenheit.

            (C) Nominal water containing capacity of 120 U.S.

        gallons.

        (5) Coil type hot water boilers where the water can

    flash into steam when released directly to the atmosphere through a manually operated nozzle provided the following conditions are met:

            (A) There is no drum, headers, or other steam

        space.

            (B) No steam is generated within the coil.

            (C) Outside diameter of tubing does not exceed 1

        inch.

            (D) Pipe size does not exceed 3/4 inch NPS.

            (E) Water capacity of unit does not exceed 6 U.S.

        gallons.

            (F) Water temperature does not exceed 350 degrees

        Fahrenheit.

        (6) Pressure vessels containing only water under

    pressure for domestic supply purposes, including those containing air, the compression of which serves only a cushion or airlift pumping function.

        (7) Pressure vessels operated at a pressure not

    exceeding 15 psig with no limitation on size.

        (8) Pressure vessels that do not exceed:

            (A) Both a volume of 15 cubic feet and 250 psig

        when not located in a place of public assembly.

            (B) Both a volume of 5 cubic and 250 psig when

        located in a place of public assembly.

            (C) A volume of 1 1/2 cubic feet or an inside

        diameter of 6 inches with no limitation on pressure.

        (9) Water conditioning equipment used for the removal

    of minerals, chemicals, or organic or inorganic particles from water by means other than application of heat including, without limitation, water softeners, water filters, dealkalizers, and demineralizers.

        (10) Steam boilers of railroad locomotives and

    traction engines built prior to 1955 that were constructed or operated in compliance with the Federal Locomotive Inspection Law and are in the permanent collection of a museum or historical association are exempt from the requirements of subsection (c) of Section 10 upon proof of such construction or inspection being furnished to the Board.

    (c) (Blank).

(Source: P.A. 98-756, eff. 7-16-14.)