Ex Parte STEINER et al - Page 2




             Appeal No. 2002-0496                                                              Page 2                
             Application No. 09/182,542                                                                              


                    When a section of cable fails, it causes a blackout.  To return power to                         
             customers, a repair crew must find the failed section of cable and reconnect the                        
             transformers on either side thereof with a working section of cable.  Conventionally,                   
             explain the appellants, a faulted circuit indicator ("FCI") is installed on the cable at each           
             transformer enclosure to assist the repair crew as follows.  Power is supplied to the                   
             cable from one end only, viz., the "feed point."  The other end is left open, viz., the                 
             "open point".  When a cable fails, a large over current passes through the cable from                   
             the feed point into the fault.  The over current trips each FCI located between the feed                
             point and the fault.  The FCIs in the transformer enclosures between the open point and                 
             the fault do not trip because no over current flows through these cable sections.  The                  
             repair crew examines each FCI until it locates the last tripped FCI and the first                       
             "untripped" FCI; the failed cable section lies therebetween.  (Id. at 1-2.)                             


                    Unfortunately, the larger the URD, the larger the number of FCIs needed to                       
             monitor the system.  The appellants also add that "traditional FCIs . . . are expensive to              
             install, time consuming to operate and somewhat unreliable."  (Id. at 2.)                               


                    Accordingly, the appellants' use a fault distance indicator ("FDI") to determine                 
             the location of a fault on each half of a URD loop.  For each half, an FDI is placed at the             
             junction between two of sections of cable.  After a fault occurs in a half, the associated              








Page:  Previous  1  2  3  4  5  6  7  8  9  10  11  Next 

Last modified: November 3, 2007