Appeal No. 2002-0496 Page 2 Application No. 09/182,542 When a section of cable fails, it causes a blackout. To return power to customers, a repair crew must find the failed section of cable and reconnect the transformers on either side thereof with a working section of cable. Conventionally, explain the appellants, a faulted circuit indicator ("FCI") is installed on the cable at each transformer enclosure to assist the repair crew as follows. Power is supplied to the cable from one end only, viz., the "feed point." The other end is left open, viz., the "open point". When a cable fails, a large over current passes through the cable from the feed point into the fault. The over current trips each FCI located between the feed point and the fault. The FCIs in the transformer enclosures between the open point and the fault do not trip because no over current flows through these cable sections. The repair crew examines each FCI until it locates the last tripped FCI and the first "untripped" FCI; the failed cable section lies therebetween. (Id. at 1-2.) Unfortunately, the larger the URD, the larger the number of FCIs needed to monitor the system. The appellants also add that "traditional FCIs . . . are expensive to install, time consuming to operate and somewhat unreliable." (Id. at 2.) Accordingly, the appellants' use a fault distance indicator ("FDI") to determine the location of a fault on each half of a URD loop. For each half, an FDI is placed at the junction between two of sections of cable. After a fault occurs in a half, the associatedPage: Previous 1 2 3 4 5 6 7 8 9 10 11 NextLast modified: November 3, 2007