Appeal No. 97-1243 Application 08/443,301 anticipated by or, in the alternative, under 35 U.S.C. § 103 as being obvious over Stocker. The examiner considers that Stocker discloses in Figure 7 a pump that corresponds to the pump set forth in claim 1 with the possible exception of the venting of the electromagnetic valve. With respect to this feature, the examiner considers that “[t]he electromagnetic valve of the device shown in Fig. 7 of . . . [Stocker] appears to be vented. In any event, it would have been obvious to one of ordinary skill in the art to vent the electromagnetic valve in order to provide cooling or dissipate heat” (final rejection, page 2). Appellant’s argument in response to the positions taken by the examiner in rejecting the appealed claim centers on the shut-off valve requirements of claim 1. For example, on pages 3-4 of the brief, appellant argues: . . . [A]ppellants fail to find the claimed shut-off valve 25 provided between the supply conduit and the delivery conduit. . . . There is no shut-off valve such as valve 25 as set forth in the claimed subject matter and shown in appellant’s Fig. 1. Since Stocker et al do not teach the valve 25, then Stocker et al cannot meet the terms of the claim[] which set[s] forth “when the shut-off valve 25 is closed, ambient air induced in the delivery space 57 is delivered via the second non-return valve 29 into the tank system.[”] Since Stocker et al do not -3-Page: Previous 1 2 3 4 5 6 7 8 9 10 NextLast modified: November 3, 2007